XM31-915-HP
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Diagnostics
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V1.07.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
117.24
V
Current
7.19
A
Power
759
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
9,543
Wh
1
Output
Voltage
87.26
V
Power
641
W
Apparent Power
704.18
VA
Frequency
60.04
Hz
Percent Load
53.80
%
Output Setting
90 V
Output Regulation
Coarse override
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
8.07
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Disable
Total Standby Events
89
Time Since Last Standby Event
32d 18h:51m
Time in Last Standby Event
0d 0h:04m
Total Time in Standby
1,938
min
Standby Events Since Reset
60
Time in Standby Since Reset
1,594
min
Time Since Reset
406
day(s)
Total Run Time
406
day(s)
Transformer Run Time
406
day(s)
Total Downtime
1d 1h:51m
Oil Cap Lifespan Consumed
11.8
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
27
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2025 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com
Close