XM31-915-HP
Power Supply Events
 
 

Alarms
 

Battery
 

Displayed time zone:
<<Prev 1 2 3 4 5 6 7 8 Next>>
Power Supply Events
  Time Event Description
642 2025-12-16 02:48:23 2001 02:00:36 12/16/25 47m UTILITY EVENT: OUTAGE
641 2025-12-16 02:48:22 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
640 2025-12-16 02:48:22 2029 MAJOR ALARM :XM3-1 Low Batt Disconnect=STRING
639 2025-12-16 02:28:19 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
638 2025-12-16 02:28:10 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
637 2025-12-16 02:24:04 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
636 2025-12-16 02:01:09 202B ALARM CLEARED :XM3-1 STRING A MISWIRED=0
635 2025-12-16 02:00:39 202A MINOR ALARM :XM3-1 STRING A MISWIRED=1
634 2025-12-16 02:00:34 202A MINOR ALARM :XM3-1 STRING A MISWIRED=2
633 2025-12-16 01:51:47 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
632 2025-12-16 01:51:38 2001 22:59:30 12/15/25172m UTILITY EVENT: OUTAGE
631 2025-12-16 01:44:41 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
630 2025-12-16 01:42:07 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
629 2025-12-15 22:59:28 2001 22:59:23 12/15/25 5s UTILITY EVENT: OUTAGE
628 2025-12-15 22:59:22 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
627 2025-12-15 22:59:19 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
626 2025-12-15 22:59:14 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
625 2025-11-20 19:27:38 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
624 2025-11-20 19:27:08 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
623 2025-11-18 02:13:00 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
622 2025-11-18 02:12:54 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
621 2025-11-14 19:52:27 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
620 2025-11-14 19:51:57 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
619 2025-11-07 00:33:09 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
618 2025-11-07 00:33:04 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
617 2025-10-29 14:05:05 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
616 2025-10-29 14:05:00 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
615 2025-10-26 00:12:28 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
614 2025-10-26 00:12:22 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
613 2025-10-24 21:28:44 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
612 2025-10-24 21:28:37 2001 20:19:14 10/24/25 69m UTILITY EVENT: OUTAGE
611 2025-10-24 20:19:12 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
610 2025-10-20 04:20:25 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
609 2025-10-20 04:20:16 2001 04:19:38 10/20/25 38s UTILITY EVENT: OUTAGE
608 2025-10-20 04:19:37 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
607 2025-10-17 11:34:53 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
606 2025-10-17 11:34:48 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
605 2025-10-17 09:24:34 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
604 2025-10-17 09:24:03 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
603 2025-10-14 15:06:28 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
602 2025-10-14 15:06:22 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
601 2025-10-14 15:05:54 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
600 2025-10-14 15:05:47 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
599 2025-10-13 14:38:32 202B <5>ALARM CLEARED :XM3-1 STRING A MISWIRED=0
598 2025-10-13 14:38:31 202A <5>MINOR ALARM :XM3-1 STRING A MISWIRED=1
597 2025-10-13 14:38:30 202B <2>ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
596 2025-10-13 14:38:29 202A <2>MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
595 2025-10-13 14:00:11 2038 ALARM CLEARED :XM3-1 ACTIVE DROP =0 NEW: 660W, OLD: 633W
594 2025-10-13 08:23:57 202B ALARM CLEARED :XM3-1 Low Batt Disconnect=OK
593 2025-10-13 08:18:20 201A ALARM CLEARED :XM3-1 OUTPUT FAIL ALARM=OK
592 2025-10-13 08:04:15 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
591 2025-10-13 08:00:40 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
590 2025-10-13 08:00:15 201A MAJOR ALARM :XM3-1 OUTPUT FAIL ALARM=ALARM
589 2025-10-13 08:00:08 2001 07:27:09 10/13/25 32m UTILITY EVENT: OUTAGE
588 2025-10-13 08:00:07 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
587 2025-10-13 08:00:06 2029 MAJOR ALARM :XM3-1 Low Batt Disconnect=STRING
586 2025-10-13 07:39:51 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
585 2025-10-13 07:10:57 202B ALARM CLEARED :XM3-1 Low Batt Disconnect=OK
584 2025-10-13 07:05:41 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
583 2025-10-13 07:05:37 201A ALARM CLEARED :XM3-1 OUTPUT FAIL ALARM=OK
582 2025-10-13 07:04:54 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
581 2025-10-13 07:00:48 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
580 2025-10-13 07:00:35 201A MAJOR ALARM :XM3-1 OUTPUT FAIL ALARM=ALARM
579 2025-10-13 07:00:31 2038 WARNING :XM3-1 ACTIVE DROP =1 NEW: 0W, OLD: 663W
578 2025-10-13 07:00:29 2001 04:43:09 10/13/25137m UTILITY EVENT: OUTAGE
577 2025-10-13 07:00:27 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
576 2025-10-13 07:00:26 2029 MAJOR ALARM :XM3-1 Low Batt Disconnect=STRING
575 2025-10-13 06:27:46 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
574 2025-10-13 06:25:34 202B ALARM CLEARED :XM3-1 STRING A MISWIRED=0
573 2025-10-13 06:25:29 202A MINOR ALARM :XM3-1 STRING A MISWIRED=1
572 2025-10-13 06:24:49 202B ALARM CLEARED :XM3-1 STRING A MISWIRED=0
571 2025-10-13 06:24:44 202A MINOR ALARM :XM3-1 STRING A MISWIRED=1
570 2025-10-13 04:43:08 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
569 2025-10-13 03:13:49 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
568 2025-10-13 03:13:41 2001 01:00:15 10/13/25133m UTILITY EVENT: OUTAGE
567 2025-10-13 01:00:14 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
566 2025-10-11 20:25:18 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
565 2025-10-11 20:24:48 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
564 2025-10-10 13:31:19 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
563 2025-10-10 13:30:48 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
562 2025-10-02 10:24:32 200A TIME SET 10:23:31 10/02/25
561 2025-10-02 07:08:25 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
560 2025-10-02 07:05:21 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
559 2025-10-01 01:18:49 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
558 2025-10-01 01:18:41 2001 01:17:48 10/01/25 53s UTILITY EVENT: OUTAGE
557 2025-10-01 01:17:46 2001 01:17:41 10/01/25 5s UTILITY EVENT: OUTAGE
556 2025-10-01 01:17:39 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
555 2025-10-01 01:17:32 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
554 2025-10-01 01:17:22 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
553 2025-09-11 16:56:04 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
552 2025-09-11 16:55:55 2001 14:54:35 09/11/25121m UTILITY EVENT: OUTAGE
551 2025-09-11 14:54:33 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
550 2025-09-09 06:51:30 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
549 2025-09-09 06:50:59 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
548 2025-08-29 17:32:15 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
547 2025-08-29 17:28:09 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
546 2025-08-29 15:23:46 200A TIME SET 15:22:07 08/29/25
545 2025-08-29 06:34:29 202B ALARM CLEARED :XM3-1 COMMS CARD ALARM=OK
544 2025-08-29 06:30:54 202F WARNING :XM3-1 COMMS CARD ALARM=ALARM
543 2025-08-16 08:52:45 202B ALARM CLEARED :XM3-1 PDM EEPROM ERROR=OK
<<Prev 1 2 3 4 5 6 7 8 Next>>

 